BW GCW GLAND FOR SWA CABLE

CW FLAME PROOF GLAND
FOR SWA CABLE
As above but with these
additional benefits:
*For use in hazardous
Environments.
*Compiles with BS 5501 Pt 1 & Pt 6
*CW for flame proof increased
safety application.
*Threads : Entry threads are
metric to BS 364. Also
available in Imperial (ET)
*Also available in Aluminium
(BS 1474) cable glands.
• BS 6121 : Pt 1 • Suitable for single wire armoured, plastic or rubber
sheathed cables. • Outer seal grips sheath of cable. • For use in most
climatic conditions, weather proof and water proof. • Seal rated to
Ip 66. • Design has seperated armour locking ring. • Gland rated to
Ip 66 with use of suitable sealing washer or thread sealant at gland
interface. • Finish : Natural Brass. Also in Electro Tinned and Nickel.
Category:
    CABLE DIMENSIONS ACCOMODATED GLAND DIMENSIONS
COMP

NO.

SIZE DIAMETER ARMOUR

WIRE

DIAMETER

C

SO ENTRY

THREAD

DIA LENGTH

D              E

APP. LENGTH

FROM

SHOULDER

F

HEXAGON SIZE

ACROSS 

FLAT

           G 

 

 
UNDER

ARMOUR

A

OVERALL

B

ACROSS

CORNERS

H

    MIN MAX MAX            
    mm mm mm mm mm mm mm mm mm
MCW – 16 16 8:6 13:2 0:9 16 10 40 23:4 26:7
MCW – 20SS 20SS 8:6 13:2 0:9 20 10 40 23:4 26:7
MCW – 20S 20S 11:6 15:8 0:9/1:25 20 10 42 25:7 29:2
MCW – 20L 20L 13:9 20:8 0:9/1:25 20 10 42 30:5 34:0
MCW – 25S 25S 15:5 25:8 0:9/1:25 25 10 48 37:6 42:2
MCW – 25L 25L 19:9 27:2 0:9/1:25 25 10 48 37:6 42:2
MCW – 32 32 26:2 33:5 1:60/2:0 32 10 51 47:3 53:6
MCW – 40S 40S 30:3 35:9 1:60/2:0 40 10 55 56:7 61:5
MCW – 40L 40L 32:1 39:9 1:60/2:0 40 15 55 56:7 61:5
MCW – 50S 50S 40:8 51:0 2:0/2:25 50 15 60 70:1 77:2
MCW – 50L 50L 44:0 52:6 2:0/2:25 50 15 60 70:1 77:2
MCW – 63S 63S 53:6 64:1 2:5 63 15 63 80:0 87:4
MCW – 63M 63M 55:9 65:3 2:5 63 15 63 80:0 87:4
MCW – 75L 75L 67:9 78:0 2:5 75 15 72 98:8 109:2
MCW – 85L 85L   74:0 88:0 3:15 85 20 106 115:0 126:0

Download Catalogue


    This will close in 0 seconds